Multi-function input
terminal status
* Displayed as on the keypad.
Multi-function Input Terminal Control Setting Details
In.84 DI Delay Sel
Select whether or not to activate the time values set at In.85 and In.86. If
deactivated, the time values are set to the default values at In.85 and In.86. If
activated, the set time values at In.85 and In.86 are set to the corresponding
terminals.
B terminal status (Normally
Closed)
A terminal status (Normally
Open)
In.85 DI On Delay,
In.86 DI Off Delay
If the input terminal’s state is not changed during the set time, when the terminal
receives an input, it is recognized as On or Off.
In.87 DI NC/NO Sel
Select terminal contact types for each input terminal. The position of the
indicator light corresponds to the segment that is on as shown in the table below.
With the bottom segment on, it indicates that the terminal is configured as a A
terminal (Normally Open) contact. With the top segment on, it indicates that the
terminal is configured as a B terminal (Normally Closed) contact. Terminals are
numbered P1
–P7, from right to left.
B terminal status (Normally
Closed)
A terminal status (Normally
Open)
In.90 DI Status
Display the configuration of each contact. When a segment is configured as A
terminal using dr.87, the On condition is indicated by the top segment turning on.
The Off condition is indicated when the bottom segment is turned on. When
contacts are configured as B terminals, the segment lights behave conversely.
Terminals are numbered P1
–P7, from right to left.