80 User function output 16 User Output 16 0
-32767–32767
-
81 User function 17 User Func17 0
0–28
-
82 User function input 17-A User Input 17-A 0
0–0xFFFF
-
83 User function input 17-B User Input 17-B 0
0–0xFFFF
-
84 User function input 17-C User Input 17-C 0
0–0xFFFF
-
85 User function output 17 User Output 17 0
-32767–32767
-
86 User function 18 User Func18 0
0–28
-
87 User function input 18-A User Input 18-A 0
0–0xFFFF
-
88 User function input 18-B User Input 18-B 0
0–0xFFFF
-
89 User function input 18-C User Input 18-C 0
0–0xFFFF
-
90 User function output 18 User Output 18 0
-32767–32767
-
User Sequence Setting Details
Display the parameter groups related to a user sequence.
US.01 User Seq Con
Set Sequence Run and Sequence Stop with the keypad.
Parameters cannot be adjusted during an operation. To adjust parameters,
the operation must be stopped.
US.02 User Loop Time
Set the user sequence Loop Time.
User sequence loop time can be set to 0.01s/0.02s/ 0.05s/0.1s/0.5s/1s.
US.11–28
Link UserOut1–18
Set parameters to connect 18 Function Blocks. If the input value is 0x0000,
an output value cannot be used.
To use the output value in step 1 for the frequency reference (Cmd
Frequency), input the communication address(0x1101) of the Cmd
frequency as the Link UserOut1 parameter.
US.31–60 Void Para1–30
Set 30 void parameters. Use when constant (Const) parameter input is
needed in the user function block.
UF.01–90
Set user defined functions for the 18 function blocks.
If the function block setting is invalid, the output of the User Output@ is -1.
All the outputs from the User Output@ are read only, and can be used with
the user output link@ (Link UserOut@) of the US group.
Function Block Parameter Structure
Choose the function to perform in the function block.
Communication address of the function’s first input parameter.
Communication address of the function’s second input parameter.
Communication address of the function’s third input parameter.