132
Learning Advanced Features
Safe Operation Mode Setting Details
Code
Description
In.6569 Px Define
From the multi-function terminals, select a terminal to operate in safe operation
mode and set it to 13 (RUN Enable).
Ad.70 Run En Mode
Setting
Function
0
Always Enable
Enables safe operation mode.
1
DI Dependent
Recognizes the operation command from a multi-
function input terminal.
Ad.71 Run Dis Stop
Set the operation of the inverter when the multi-function input terminal in safe
operation mode is off.
Setting
Function
1
Free-Run
Blocks the inverter output when the multi-
function terminal is off.
2
Q-Stop
The deceleration time (Q-Stop Time) used in safe
operation mode. It stops after deceleration and
then the operation can resume only when the
operation command is entered again. The
operation will not begin if only the multi-function
terminal is on.
3
Q-Stop
Resume
The inverter decelerates to the deceleration time
(Q-Stop Time) in safe operation mode. It stops after
deceleration. Then if the multi-function terminal is
on, the operation resumes as soon as the
operation command is entered again.
Ad.72 Q-Stop Time
Sets the deceleration time when Ad.71 (Run Dis Stop) is set to 1 (Q-Stop) or 2
(Q-Stop Resume).