140
Learning Advanced Features
Note
When the PID switch operation (switching from PID operation to general operation) enters the multi-
function input, [%] values are converted to [Hz] values. The normal PID output, PID OUT, is unipolar, and
is limited by AP.29 (PID Limit Hi) and AP.30 (PID Limit Lo). A calculation of 100.0% is based on the dr.20
(Max Freq) parameter setting.