Learning Advanced Features
145
Auto Tuning Default Parameter Setting
Motor Capacity
(kW)
Rated Current
(A)
No-load
Current (A)
Rated Slip
Frequency(Hz)
Stator
Resistance(
)
Leakage
Inductance (mH)
200V
0.2
1.1
0.8
3.33
14.0
40.4
0.4
2.4
1.4
3.33
6.70
26.9
0.75
3.4
1.7
3.00
2.600
17.94
1.5
6.4
2.6
2.67
1.170
9.29
2.2
8.6
3.3
2.33
0.840
6.63
3.7
13.8
5.0
2.33
0.500
4.48
5.5
21.0
7.1
1.50
0.314
3.19
7.5
28.2
9.3
1.33
0.169
2.844
11
40.0
12.4
1.00
0.120
1.488
15
53.6
15.5
1.00
0.084
1.118
18.5
65.6
19.0
1.00
0.068
0.819
22
76.8
21.5
1.00
0.056
0.948
400V
0.2
0.7
0.5
3.33
28.00
121.2
0.4
1.4
0.8
3.33
14.0
80.8
0.75
2.0
1.0
3.00
7.81
53.9
1.5
3.7
1.5
2.67
3.52
27.9
2.2
5.0
1.9
2.33
2.520
19.95
3.7
8.0
2.9
2.33
1.500
13.45
5.5
12.1
4.1
1.50
0.940
9.62
7.5
16.3
5.4
1.33
0.520
8.53
11
23.2
7.2
1.00
0.360
4.48
15
31.0
9.0
1.00
0.250
3.38
18.5
38.0
11.0
1.00
0.168
2.457
22
44.5
12.5
1.00
0.168
2.844
*When Dr.09 (Control Mode) is set to 6 (PM Sensorless), auto tuning will configure the rated
current and the stator resistor values by default.
Auto Tuning Parameter Setting Details
Code
Description
bA.20 Auto Tuning
Select an auto tuning type and run it. Select one of the options and then press the
[ENT] key to run the auto tuning.
Setting
Function
0
None
Auto tuning function is not enabled. Also, if you select
one of the auto tuning options and run it, the parameter
value will revert back to 0” when the auto tuning is