164
Learning Advanced Features
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
78
Kinetic energy buffering
start level
KEB Start Lev 125.0 110.0~200.0 %
79
Kinetic energy buffering
stop level
KEB Stop Lev 130.0 Cn-78~210.0 %
80
Energy buffering P gain
KEB P Gain
1000
0-20000
81
Energy buffering
I gain
KEB I Gain 500 1~20000
82
Energy buffering
Slip gain
KEB Slip Gain 30.0 0~2000.0%
83
Energy buffering
acceleration time
KEB Acc Time 10.0 0.0~600.0(s) -
In
65
~71
Pn terminal function setting Pn Define 52 KEB-1 Select - -
Kinetic Energy Buffering Operation Setting Details
Code
Description
Cn.77 KEB Select
Select the kinetic energy buffering operation when the input power is
disconnected. If 1 or 2 is selected, it controls the inverter's output frequency
and charges the DC link (inverter's DC part) with energy generated from the
motor. Also, this function can be set using a terminal input. From the Pn
terminal function settings, select KEB-1 Select, and then turn on the terminal
block to run the KEB-1 function. (If KEB-1 Select is selected, KEB-1 or KEB-2
cannot be set in Cn-77.)
Setting
Function
0
None
General deceleration is carried out until a low voltage trip
occurs.
1
KEB-1
When the input power is blocked, it charges the DC link with
regenerated energy. When the input power is restored, it
restores normal operation from the energy buffering
operation to the frequency reference operation. KEB Acc
Time in Cn-89 is applied as the operation frequency
acceleration time when restoring to the normal operation.
2
KEB-2
When the input power is blocked, it charges the DC link with
regenerated energy. When the input power is restored, it
changes from the energy buffering operation to the
deceleration stop operation. The Dec Time in dr-04 is applied
as the operation frequency deceleration time during the
deceleration stop operation.
[KEB-1]