LSIS LSLV-S100 - Protection Function group (PAR→Pr)

LSIS LSLV-S100
411 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
345
Type
Cause
Remedy
not increase to
the frequency
reference.
The frequency reference is exceeding the
upper limit of the frequency command.
Set the upper limit of the frequency
command higher than the frequency
reference.
Because the load is too heavy, the stall
prevention function is working.
Replace the inverter with a model with
increased capacity.
The cooling fan
does not rotate.
The control parameter for the cooling fan
is set incorrectly.
Check the control parameter setting for
the cooling fan.