LumaSMART
®
User Manual Modbus Protocol Testing • 95
119
0 = Disabled
1 = Normally Deenergized
Int16
Relay 12
120 Alarm Set Point for Relay 12 Int16
121 Restore Set Point for Relay 12 Int16
122
Channels Driving Relay 12
MSB = CH16 / LSB = CH1
123
Control Setting for Relay Number 12
2 = OR Logic
Int16
124
0 = Disabled
1 = Normally Deenergized
Int16
Relay 13
125 Alarm Set Point for Relay 13 Int16
126 Restore Set Point for Relay 13 Int16
127
Channels Driving Relay 13
MSB = CH16 / LSB = CH1
128
Control Setting for Relay Number 13
2 = OR Logic
Int16
129
0 = Disabled
1 = Normally Deenergized
Int16
Relay 14
130 Alarm Set Point for Relay 14 Int16
131 Restore Set Point for Relay 14 Int16
132
Channels Driving Relay 14
MSB = CH16 / LSB = CH1
133
Control Setting for Relay Number 14
2 = OR Logic
1 = AVG Logic
Int16