Megger Baker DX - Surge Tests Using the DX Host

Megger Baker DX
156 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Procedures for Testing with the DX Host
megger.com 67
Capacitance Test Procedures
This procedure starts from the end of the inductance test, but can start from the end of
the resistance test as well.
The DX measures the capacitance of the core across the ground wall insulation.
Modify connections of the RLC test leads to a capacitor test configuration.
1. Connect RLC test lead 1 to any motor lead.
2. Connect RLC test lead 2 to ground.
3. Disconnect RLC test lead 3 and leave disconnected.
Figure 71. Capacitance test lead connections.