Bytes 063
Name Type of data Function
Byte 1
Bit 0: MSB
Bit 0: start lling
Bit 1: stop lling
Bit 2: restart lling
Bit 3: cancel lling
Bit 4: load material and start l-
ling
Bit 5: print last lling result
Bit 6: reserved
Bit 7: reserved
BOOL Bit 0:
EasyFill adopts the sent material parame-
ters from byte 4 with the rising edge of this
bit. A valid set point (byte 47) that can be
coded as DINT or REAL is required.
The lling process can be started when the
ready bit is set.
Bit 1:
rising edge during lling
Bit 2:
rising edge in the stop status (hold state)
Bit 3:
rising edge in the stop status (hold state)
Bit 4:
rising edge: A valid material ID is required
in byte 3.
Bit 5:
rising edge: The printout of the last lling
result starts.
Byte 2 Bit 0: reset power failure (power
fail)
Bit 1: reset error
Bit 2: weights as DINT
Bit 3: zero
Bit 4: tare
Bit 5: reset tare
Bit 6: lling mode
Bit 7: read material from the
material table
BOOL Bit 0:
rising edge
Bit 1:
rising edge: resets the error ag and error
code.
Bit 2:
status-controlled:
Value: 0 = Real, 1 = DINT
Bit 3:
rising edge
Bit 4:
rising edge
Bit 5:
rising edge
Bit 6:
status-controlled: 0 = ll, 1 = empty
Bit 7:
rising edge: A valid material ID is required
in byte 3. Filling does not start.
This function can be used to display materi-
al parameters on external displays.
Byte 3 Material ID BYTE
Value range: 110
Byte 47
Set point DINT/REAL Weight
Byte 811
Preset DINT/REAL Preset point for switching from coarse ow
to ne ow.
Byte 1215
Material overshoot (OVS) DINT/REAL Weight
Byte 1619
Calming time DINT [ms]
Transmitter in eld housing PR 5230 12 Fieldbus interface
Minebea Intec EN-272