Filling starts again with the rising edge and the system leaves the hold status (hold state)
and goes back to the ready status (ready/idle).
12.3.4.3 Filling report
The lling results are stored after lling and only overwritten when there is a new result.
12.3.4.4 Filling error
Last_Error
The last error number is retained until it is reset.
The possible error numbers are listed in Chapter 16.8.2.
12.3.4.5 Reading the material table
The material parameters can be read from the material table of the device (PR 5230).
Procedure:
12.3.5 Setup of the eldbus interface
For description of the data types see Chapter 13.2.
12.3.5.1 PLC → write window EasyFill
Bytes 063
Name Type of data Function
Byte 0 TableSelect USINT The rst byte controls (multiplexes) the da-
ta written in the read window by the device.
A "0" describes the read window according
to the system data layout.
A "1" copies the material data to the read
window.
1. Write the material ID to byte 3.
2. Write command 1 to byte 0 in order to see the material parameters on the read side.
3. Write command 0000 0001 to byte 2 in order to copy the material parameters from
the material table.
If all parameters of the material were available to be read, 1000 0000 is set to
byte 2.
4. Write command 0 to byte 0 in order to see the lling parameters again on the read
side.