OPERATION
© 2014 Mold-Masters (2007) Limited. All Rights Reserved.
Revised 1 Oct, 2014
6-3
www.moldmasters.com
6.2 Control Modes for all zones
(from the Display Page)
Operation Available
by
Description
RUN
Button One
or Mode
Button
Switches on all zones.
STOP
Button Two
or Mode
Button
Switches off all zones.
NOTE: Selecting Stop does not remove voltage
from the heaters; it switches off by setting all
the target temperatures to Zero. Do NOT try to
change fuses or disconnect units while in this
mode.
STANDBY
Button One
or Mode
Button
Reduces the temperature of all zones that have
any Standby Temperature congured on the
Setup page.
Temperature remains reduced until RUN
command is given.
STARTUP
Button One
or Mode
Button
STARTUP
Initiates a starting sequence that is congured
on the Setup page.
MASTER-FOLLOW – Applies power to Master
zones then adjusts other zones’ Set Temp to
follow Master Zones’ Actual Temperature –
produces a homogeneous heat rise.
MASTER-ONLY – applies power to Master
Zones but waits until they are at full
temperature before switching on all others.
STAGED – applies power to nominated stage
zones and then waits until they reach normal
temperature before switching on next stage
zones. This cascades the startup sequence
through several stages.
SECOND STARTUP
When all the zones have reached their set
temperatures the system then goes into
SECOND STARTUP mode which may be
congured to either:
RUN – maintain their Set Temperature.
BOOST – temporarily raise the temperature
and then settle back to normal Set
Temperature.
STANDBY – lower zone temperatures until Run
command is given.