Connecting Releasing Devices Releasing Applications
AFP-200 PN 15511:H2 10/14/2002 155
Figure 146 Typical Connections for an Agent Release-Abort Station
Note:
For releasing applications use an end-of-line device (part number REL-47K) with
the control module.
All wiring for releasing circuits is supervised against open and shorts.
Connect the end-of-line device as shown in Figure 146.
Program the module or NAC for REL CKT ULC type code.
+ +
– –
+ +
+
+
+
1
2
4
6
5
7
6
1
2
3
4
SLC loop to AFP-200
TB6-5 (-)
TB6-3 (+)
24 VDC power
from AFP-200
TB1-2 (-)
TB1-1 (+)
FCM-1
FRM-1
FMM-101
FMM-101
Black
Red
Yellow
Violet
Black
Red
Yellow
Violet
AFP-200 TB1-1
+24 VDC
Manual Abort
Manual Release
Normal
Release
NBG-12LRA
See Document 51369
for installation details.
ELR mode R-47K
supervised and
power-limited
Red
Brown
24 VDC UL-listed
releasing device
Power Supervision
Relay A77-716B
C.
N.C. N.O.
REL-47K
end-of-line device
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFP-200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-200 and is the answer not in the manual?

Notifier AFP-200 Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
Auxiliary Power Output24 VDC, 500 mA
Operating Temperature32°F to 120°F (0°C to 49°C)
Display80-character LCD
Power Supply120 VAC, 60 Hz
Capacity198 addressable devices
Notification Appliance Circuits2
Relay Contacts3 (Form-C)
Relative Humidity93% non-condensing

Related product manuals