EasyManuals Logo

Omron E5EK User Manual

Omron E5EK
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #123 background imageLoading...
Page #123 background image
6.4 Commands and Responses
E5EK
6--9
Parameter No. Parameter Data Setting Range Mode
28 Set point upper limit
*1
Set point lower li mi t +1 to scaling upper limit
27 Set point lower limit
*1
Scali ng lower limi t to Set point upper li mi t -1
72 PID / ON/OFF
0: Advanced PID, 1: ON/OFF
73 ST
0:OFF, 1:ON
34 ST stable range width
0.1 to 999.9
35 α
0.00 to 1.00
Expansion
85 AT calculated gain
0.1 to 10.0
37 Standby sequence reset method
0, 1
36 Automatic return of display mode
0to99
93 AT hysteresis
0.1to9.9
55 LBA detection width
0.0 to 999.9
82 HBA latch
0: OFF, 1: ON
89 Travel time
1to999
38 PV dead band
0 to 9999
29 Remote SP enable
0: Enabled, 1: Disabled
Option
91 Remote SP upper limit
SP setting lower limit to SP setting upper limit
90 Remote SP lower limit
SP setting lower limit to SP setting upper limit
39 SP tracking
0: OFF, 1: ON
*1 During temperature input, the range becomes the range of use of the selected sensor instead of the scaling upper/lower limit
values
*2 See page 5-35.
*2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EK and is the answer not in the manual?

Omron E5EK Specifications

General IconGeneral
BrandOmron
ModelE5EK
CategoryController
LanguageEnglish

Related product manuals