APPENDIX
E5EK
A-- 4
JOutput Unit Ratings and Characteristics
Ratings and characteristics conform to the output unit mounted on the
controller. For details on the ratings of the output unit, see page 2---9.
The relay output unit is already mounted on the E5EK-PRR2. When
replacing the output unit, use the E53-R.
JOption Unit Ratings and Characteristics
Contact input ON: 1 kΩ max., OFF: 100 kΩ min.
Event inputs
No-contact input
ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA
max.
Communications
Interface :RS-232C, RS-422 or RS-485
Transmission method :Half-duplex
Synchronization method :Start-stop synchronization (asynchronous method)
Baud rate :1.2/2.4/4.8/9.6/19.2 kbps
Transfer output 4 to 20 mA, Permissible load impedance: 600 Ω max. Resolution: Approx. 2600