Section 1 Overview 1-3 Communicating with the Host
1-24
NS Series Programming Manual
Address Operation Classification
15 Notification/Control of Video NS status notification
and control
16 Port A NT Link Priority Registration (for 1:N)
17 Port B NT Link Priority Registration (for 1:N)
NS status control
18 Ten Key Pad Display with Temporary Input NS status control
19 Input Disable (ON: Disabled, OFF: Enabled)
To clear input disable, touch the screen and enter the password for
the password level set under $SW13 in the dialog box that will be
displayed prompting password input.
NS status control
20 Contrast Adjustment (+10 levels) (NS5 only)
21 Contrast Adjustment (+1 level) (NS5 only)
22
Contrast Adjustment (−1 level) (NS5 only)
23
Contrast Adjustment (−10 levels) (NS5 only)
NS status control
24 Video Capture NS status notification
and control
25 Start Printing/Capture Screen
26 Stop Printing
27 Test Pattern Printing
28 Printer head-cleaning (Ignored for PictBridge.)
29 Update Printer Status
NS status control
30 Printer Busy Status/Capture Busy Status NS status notification
31 Notification of Printer Error/Capture Screen Error NS status notification
32 Alarm/Event History Initialization
(Executed when ON.)
NS status notification
and control
33 Alarm/Event History Save
(Executed when ON.)
NS status notification
and control
34 Internal Holding Memory ($HB/$HW) Initialization
(Executed when ON.)
NS status notification
and control
35 Data Log Initialization
(Executed when ON.)
36 Data Log Save
(Executed when ON.)
37 Operation Log Initialization
(Executed when ON.)
38 Operation Log Save
(Executed when ON.)
NS status notification
and control
39 Functional Object Operation Log Execution
(ON: Execute, OFF: Not execute)
40 Screen Switch Operation Log Execution
(ON: Execute, OFF: Not execute)
41 Macro Execution Operation Log Execution
(ON: Execute, OFF: Not execute)
NS status control
42 Error Log Initialization
(Executed when ON.)
43 Error Log Save
(Executed when ON.)
NS status notification
and control
44 Reserved (Do not access.)
−
45 Macro Error Dialog Box Display Control
(ON: Without displaying an error dialog box, the relevant macro proc-
essing will be canceled and the previous status returned. Execu-
tion of macro processing set elsewhere will be stopped.
OFF: Displays an error dialog box, cancels the relevant macro proc-
essing, and returns the previous status. Execution of macro
processing set elsewhere will be stopped.)
NS status control