Section 2 NS Series Functions 2-4 System Memory
2-39
NS Series Programming Manual
Bit 15 8 7 0
BCD/binary: (00 fixed) day of week (00 to 06)
Sun: 00; Mon: 01: Tue: 02; Wed: 03; Thur: 04; Fri: 05; Sat: 06
No. of Alarm/Event Occurred ($SW18)
$SW18 stores the number of generated alarms and events. (Stored in BCD or binary.)
The total number of alarms and events is stored.
Alarm/Event ID Storage ($SW19, $SW20, and $SW21)
The last generated alarm or event ID number is written to $SW19. (Stored in BCD or binary.)
The last cleared alarm or event ID number is written to $SW20. (Stored in BCD or binary.)
The alarm or event ID displayed on the relevant alarm/event display object is written to $SW21 when
the Pressing a Display Area macro is executed. Alternatively, the alarm/event ID number selected
when the Selecting an Alarm/Event macro is executed for the alarm/event summary/history object is
written to $SW21. (Stored in BCD or binary.) If the macro is executed when nothing is displayed on the
alarm/event display object or alarm/event summary & history object, then nothing will be written to
$SW21.
Macro Error Number ($SW23)
The macro execution error number is stored in $SW23. There are no errors if 0 is stored in $SW23.
The error number is held until 0 is written to $SW23 from the host, using a functional object, or other
method. (Stored in BCD or binary.)
N
N
N
o
o
o
t
t
t
e
e
e
The following values are set to $SW23, depending on the macro error.
1: Program error 2: 0 allocation error
3: BCD error 4: Argument value error
The last generated macro execution error number is stored in $SW23 if macros are executed
alternatively as follows: no error, error, no error, etc.
Screen No. Having Macro Error ($SW24)
The screen number where the macro error occurred is stored in $SW24. FFFFh is stored for project
macros. (Stored in BCD or binary.)
Object ID Having Macro Error ($SW25)
The ID number of the functional object where the macro error occurred is stored in $SW25. FFFFh is
stored for project/screen macros. (Stored in BCD or binary.)
Macro Timing Having Error ($SW26)
The macro execution timing when the macro error occurred is stored in $SW26. (Stored in BCD or bi-
nary.)
0 (0): When loading a project
4 (4): Alarm/Event ON
5 (5): Alarm/Event OFF
16 (10): When loading a screen
17(11): When unloading a screen
32 (20): Touch ON
33 (21): Touch OFF

Table of Contents

Other manuals for Omron NS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NS and is the answer not in the manual?

Omron NS Specifications

General IconGeneral
Power Supply24 VDC
Display Size5.7 to 12.1 inches (depending on the model)
Resolution320 x 240 to 800 x 600
Touchscreen TypeResistive
Display TypeTFT LCD
Communication InterfacesRS-232C, RS-422/485, Ethernet, USB
MemoryFlash memory
Operating Temperature0 to 50°C (depending on the model)
Storage Temperature-20°C to 60°C
Protection RatingIP65 (front panel)
DimensionsVaries depending on the model
WeightVaries depending on the model
CPUProprietary Omron CPU (performance varies depending on the model)

Related product manuals