6-78
Setting Control modeFunctionSetting
Flux
Vector
Open-loop
Vector
V/f
w/PG
V/f
Function
1F Terminal 13/14 Switch (Selects terminal 14 when ON.) OK OK OK OK
20 to
2F
External Fault
(Any combination of the following can be set as needed.)
Input: Normally open or normally closed
Detection mode: Always or During operation only
Stopping method: Decel, Coast, Emergency, or Continue
OK OK OK OK
30 PID Integral Reset (ON: Resets the integral value with I
control disabled.)
OK OK OK OK
31 PID Integral Hold (ON: Retains the integral value.) OK OK OK OK
60 DC Injection Activate (Performs DC braking when ON.) OK OK OK OK
61 External search 1 (Speed search from max. frequency) OK --- OK ---
62 External search 2 (Speed search from frequency reference) OK --- OK ---
63 Energy-saving operation (according to b8-01 and b8-02) OK OK --- ---
64 to 66 Not used. (Do not input this setting.) --- --- --- ---
71 Speed Torque Control Change (Torque Control when ON.) --- --- --- OK
72 Zero-servo Command (Zero Servo operation when ON.) --- --- --- OK
77
ASR Gain Switch
ON: Use proportional gain in C5-03.
OFF: Calculate gain from C5-01, C5-03, and C5-07.
--- --- --- OK
D Parameter Settings
The
following table shows the setting information for multi-function inputs 1 through 6. These parame
-
ters cannot be changed during operation.
Parameter Display name Setting Units Default
*1
Valid access levels
number
py
g
range setting
*1
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
H1-01 Terminal 3 Sel 0 to 77 --- 24 Basic or Advanced
H1-02 Terminal 4 Sel 0 to 77 --- 14 Basic or Advanced
H1-03 Terminal 5 Sel 0 to 77 --- 3 (0) Basic or Advanced
H1-04 Terminal 6 Sel 0 to 77 --- 4 (3) Basic or Advanced
H1-05 Terminal 7 Sel 0 to 77 --- 6 (4) Basic or Advanced
H1-06 Terminal 8 Sel 0 to 77 --- 8 (6) Basic or Advanced
Note 1. The default settings in parentheses are the default settings when the Unit is initialized for
3-wire control.
Note 2. The following table shows the settings and page references for some common functions.
Advanced Operation Chapter
6