Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
b5-01
PID control
selection
0: Disabled
1:
Enabled (Deviation is
D-controlled.)
2:
Enabled (Feedback value is
D-controlled.)
3:
Enabled (Frequency
0 to 4
0 NO A A A A 6-50
PID Mode
re
deviation is D-controlled.)
4:
Enabled (Frequency
reference + PID control/
feedback value is
D-controlled.)
b5-02
Proportiona
l gain (P)
Sets P-control proportional gain
as a percentage.
0.00 to
25.00
1.00 OK A A A A 6-51
PID Gain
Note:
P-control is not performed
when the setting is 0.00.
b5-03
Integral
time (I)
Sets I-control integral time in
1-second units.
0.0 to
360.0
1.0 OK A A A A 6-51
PID I T
ime
Note:
I-control is not performed
when the setting is 0.0.
b5-04
Integral
limit (I)
Sets the I-control limit as a
percentage of the maximum
0.0 to
100.0
100.0 OK A A A A 6-51
PID I Limit
frequency.
b5-05
Differential
time (D)
Sets D-control dif
ferential time
in 1-second units.
0.00 to
10.00
0.00 OK A A A A 6-51
PID D Time
Note:
D-control is not performed
when the setting is 0.00.
b5-06
PID limit
Sets the limit after PID-control
100.0 OK A A A A 6-51
PID Limit
as a percentage of the
maximum frequency
.
100.0
b5-07
PID of
fset
adjustment
Sets the of
fset after PID-control
as a percentage of the
0.0 OK A A A A 6-52
PID Offset
maximum frequency
. 100.0
b5-08
PID primary
delay time
constant
Sets the time constant for low
pass filter for PID-control
outputs in 1-second units.
0.00 to
10.00
0.00 OK A A A A 6-52
PID Delay
Time
Note: Not usually necessary to
set.
b5-09
PID output
characteris-
tics selec-
tion
Selects whether the PID output
is reflected in positive or
negative characteristics.
0: Positive characteristics
(Increased output frequency
increases feedback value)
0, 1
0 NO A A A A 6-52
Output
Level Sel
increases feedback value)
1: Negative characteristics
(Increased output frequency
decreases feedback value)
b5-10
PID output
gain
Sets the multiplier for the final
calculation result of PID control
(PID control value).
Note:
Normally it is not neces
-
0.0 to
25.0
1.0 NO A A A A 6-53
Output
Gain
sary to change the factory
settings. Adjust the level
of PID influence when us
-
ing “Frequency reference
+ PID control.”
Parameter Lists Chapter
7