7-10
Para
meter
No.
PageControl
mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
DescriptionNamePara
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
b5-11
PID output
reverse
selection
Selects operation when the final
calculation result of PID control
is a negative value.
0: Disable reverse.
(If the result is negative, the
zero limit is imposed and
there is no rotation in
reverse.)
0, 1
0 NO A A A A 6-53
Output Rev
Sel
1:
Enable reverse.
(If the result is negative,
rotation in reverse occurs in
accordance with the result.)
Note:
The zero limit is imposed
if reverse operation is dis
-
abled in b1-04.
b5-12
Feedback
loss
detection
selection
Selects the method used to
detect that feedback has been
lost during PID control.
0: Disable feedback loss
detection.
1:
Enable feedback loss
0 to 2
0 NO A A A A 6-53
Fb los Det
Sel
detection. (Continue
operation: Alarm)
2:
Enable feedback loss
detection. (Stop output:
Protective operation)
b5-13
Feedback
loss
detection
level
Sets the detection level used
when feedback loss detection
has been enabled.
Set as a percentage of the
0 to
100
0 NO A A A A 6-54
Fb los Det
Lvl
feedback value that is produced
at the maximum frequency
.
b5-14
Feedback
loss
detection
time
Sets the detection time used
when feedback loss detection
has been enabled.
Note:
Feedback loss is detected
if the feedback value is
0.0 to
25.5
1.0 NO A A A A 6-54
Fb los Det
Time
below the level set in
b5-13 for longer than the
detection time set here.
Parameter Lists Chapter
7