7-32
H Other Options Setup: F2 to F9
Para
meter
Name
Description Setting
range
Default
setting
Chan-
ges
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
F2-01
Analog
Reference
Card
selection
Sets the functions for channels
1 to 3 which are ef
fective when
the 3G3IV
-P
AI14B Analog
Reference Card is used.
0:
3-channel individual
(Channel 1: terminal 13,
Channel 2: terminal 14,
Channel 3: terminal 16)
1:
3-channel addition (Addition
lhf
0, 1
0 NO B B B B 6-72
AI-14 Input
Sel
1:
3 channel
addition
(Addition
values are the frequency
reference)
Note:
When set to 0, select 1 for
b1-01. In this case the
multi-function input “Op
-
tion/Inverter selection”
cannot be used.
F3-01
Digital
Reference
Card input
selection
Sets the Digital Reference Card
input method.
0:
BCD 1% unit
1:
BCD 0.1% unit
2:
BCD 0.01% unit
3: BCD 1 Hz unit
4:
BCD 0.1 Hz unit
5:
BCD 0.01 Hz unit
6:
BCD special setting (5-digit
input)
7:
Binary input
Note:
Setting “6” is ef
fective
only when the 3G3FV
-
PDI16H2 is used, but the
input will be BCD and the
units will be set in o1-03 if
0 to 7
0 NO B B B B 6-72
DI Input
units will be set in o1-03 if
01-03 has been set to “2”
or higher
.
Note:
When F3-01 is set to “7”,
input the following values
as the max. frequency
.
3G3IV
-PD108: FF hex (255
decimal)
3G3FV-PD1
16H2: FFF hex
(4,095 decimal) for 12 bits or
7530 hex (30,000 decimal) for
16 bits
Parameter Lists Chapter