7-33
Para
meter
No.
PageControl
 mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
DescriptionNamePara
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
F4-01
Channel 1
output
monitor
selection
Ef
fective when an Analog
Monitor Card is used.
Monitor selection: Set the
number of the monitor item to
1 to 38
2 NO B B B B 6-73
AO Ch1
Select
be output. (U1-
)
Gain: Set the multiple of 10 V
F4-02
Channel 1
gain
for outputting monitor items.
Note:
4, 10, 11, 12, 13, 14, 25,
28 cannot be set 29 to 31
0.00 to
2.50
1.00 OK B B B B 6-73
AO Ch1
Gain
28 cannot be set. 29 to 31
are not used. When the
3G3IV-PAO12 is used
F4-03
Channel 2
output
monitor
selection
outputs of 
±
 10 V are pos
-
sible. In this case, set
H4-07 (select multi-func
-
tion analog output signal
1 to 38
3 NO B B B B 6-73
AO Ch2
Select
level) to 1. When the
3G3IV-P
AO08 is used,
onl
 outputs of 0 to 10 V
F4-04
Channel 2
gain
are possible.
0.00 to
2.50
0.50 OK B B B B 6-73
AO Ch2
Gain
F4-05
Channel 1
output
monitor
bias
Sets the bias value of channel 1
on the Analog Monitor Card. Set
as a percentage with 10 V
equivalent to 100%.
–10.0
to 10.0
0.0 OK B B B B 6-73
AO Ch1
Bias
F4-06
Channel 2
output
monitor
bias
Sets the bias value of channel 2
on the Analog Monitor Card. Set
as a percentage with 10 V
equivalent to 100%.
–10.0
to 10.0
0.0 OK B B B B 6-73
AO Ch2
Bias
F5-01
Channel 1
output
selection
Selects the function to be set for
channel 1 when a Contact
Output Card is used. The same
functions can be set as for
0 to 37
0 NO B B B B ---
D0-02 Ch1
Select
or
multi-function outputs H2-01 to
H2-03.
F5-02
Channel 2
output
selection
Selects the function to be set for
channel 1 when a Contact
Output Card is used. The same
functions can be set as for
0 to 37
1 NO B B B B ---
D0-02 Ch2
Select
or
multi-function outputs H2-01 to
H2-03.
F6-01
Digital
output
selection
Selects the digital output
method for when a Digital
Output Card is used.
0, 1
0 NO B B B B ---
D0-08
Selection
0: 8 channels individually
1: Code output (binary code)
F7-01
Output
pulse
multiple
selection
Ef
fective when a Pulse Monitor
Card is used. Sets the number
of output pulses.
0: 1F
, 1: 6F, 2: 10F, 3: 12F
, 4:
36F
Note:
F= the output frequency
displa
ed in Hz.
0 to 4
1 NO B B B B 6-73
PO-36F
Selection
.
Example: When 0 (1F) is
set, and the output fre
-
quency is 60 Hz, 60
pulses per second are
output. (50% duty)
Parameter Lists Chapter
 
7