7-36
Setting
value
PageControl modeFunctionSetting
value
Page
Flux
vector
Open loop
Vector
V/f
w/PG
V/f
Function
2 Option/Inverter selection (ON: Option) OK OK OK OK 6-79
3 Multi-step speed reference 1
When H3-05 is set to “0,” this function is
combined with “Main/auxiliary speed switch.”
OK OK OK OK 5-17
4 Multi-step speed reference 2 OK OK OK OK 5-17
5 Multi-step speed reference 3 OK OK OK OK 5-17
6 Jog frequency reference (has priority over
multi-step speed)
OK OK OK OK 5-17
7 Multi-accel/decel time 1 OK OK OK OK 5-18
8 Baseblock NO (contact a: Base block ON) OK OK OK OK 6-80
9 Baseblock NC (contact b: Base block OFF) OK OK OK OK 6-80
A Accel/decel ramp hold (ON: Accel/decel stopped,
frequency on hold)
OK OK OK OK 6-80
B OH2 alarm signal input (ON: OH2 will be
displayed)
OK OK OK OK 6-81
C Multi-function analog input selection (ON: Enable) OK OK OK OK 6-81
D V/f mode selection (ON: Speed feedback control
disabled, (normal V/f control))
--- OK --- --- 6-82
E Speed control integral reset (ON: Integral control
disabled)
--- OK --- OK 6-82
F Not used: Do not set --- --- --- --- ---
10 UP command “MOP Increase” (Always set with
the DOWN command)
OK OK OK OK 6-82
11 DOWN command “MOP Decrease” (Always set
with the UP command)
OK OK OK OK 6-82
12 FJOG command (ON: Forward rotation for jog
frequency d1-09)
OK OK OK OK 5-19
13 RJOG command (ON: Reverse rotation for jog
frequency d1-09)
OK OK OK OK 5-19
14 Fault reset (Reset when turned ON) OK OK OK OK 6-83
15 Emergency stop “Fast-stop” (Normally open
condition, When ON: Decelerate to a stop in the
emergency stop time set in c1-09)
OK OK OK OK 5-19
16 Motor 2 selection: Selection of motor 1 or motor 2
for two-motor switching control (ON: Motor 2
selected)
OK OK OK OK ---
17 Emergency stop N.C. (ON: Decelerate to a stop in
the emergency stop time set in c1-09)
OK OK OK OK 5-19
18 Timer function input (Functions are set with
b4-01, b4-02 and the timer function is set at the
same time)
OK OK OK OK 6-46
19 PID control ON/OFF (ON: PID control disabled) OK OK OK OK 6-84
1A Multi-accel/decel time 2 OK OK OK OK 5-18
1B Parameter write access (ON: Parameters can be
overwritten; OFF: All parameters other than
frequency monitor are write protected.)
OK OK OK OK 6-84
1C Trim control increase (ON: d4-02 frequencies are
added to analog frequency references.)
OK OK OK OK 6-84
Parameter Lists Chapter
7