7-37
Setting
value
PageControl modeFunctionSetting
value
Page
Flux
vector
Open loop
Vector
V/f
w/PG
V/f
Function
1D Trim control decrease (ON: d4-02 frequencies are
subtracted from analog frequency references.)
OK OK OK OK 6-84
1E Sample/hold analog frequency reference (ON:
Hold analog value)
OK OK OK OK 6-85
1F Frequency reference terminal 13/14 selection
(ON: select terminal 14)
Valid only when H3-09 is set to “1F”.
OK OK OK OK 5-19
20 to
2F
External fault (Desired settings possible)
Input mode: contact a/contact b,
Detection mode: Normal/during operation
Stopping method: Ramp to stop, coast to stop,
fast stop or continue operation.
OK OK OK OK 6-86
30 Reset PID control integration (ON: resets the PID
control integration value)
OK OK OK OK 6-54
31 Hold PID control integration (ON: maintains the
PID control integration value)
OK OK OK OK 6-54
60 DC injection braking command (ON: DC
operation)
OK OK OK OK 6-88
61 External speed search command 1: Maximum
frequency (ON: speed search)
OK --- OK --- 6-88
62 External speed search command 2: Set frequency
(ON: speed search)
OK --- OK --- 6-88
63 Energy save mode (ON: Energy-saving control
set for b8-01, b8-02)
OK OK --- --- 6-13
64 External speed search command OK OK OK OK ---
65 KEB (deceleration operation for momentary
power interruption) command (NC contact)
OK OK OK OK ---
66 KEB (deceleration operation for momentary
power interruption) command (NO contact)
OK OK OK OK ---
71 Speed/torque control change (ON: Torque control) --- --- --- OK 6-89
72 Zero-servo command (ON: Zero-servo lock) --- --- --- OK 6-89
77 Speed control (ASR) proportional gain switch
(ON: C5-03)
--- --- --- OK 6-89
H Digital Outputs: H2
Parame-
ter No
Name
Description Setting
range
Default
setting
Chan-
ges
Control mode
Page
ter No.
Display
name
range setting ges
during
opera-
tion
V/f con
-
trol
V/f with
PG
Open
loop
vector
Flux
vector
H2-01 Multi-func-
tion contact
output: ter
-
minal 9 to
10.
T
erminal 9 to 10 Sel
0 to 37
0 NO B B B B 6-91
H2-02 Multi-func-
tion output
1: terminal
25.
T
erminal 25 Sel
0 to 37
1 NO B B B B 6-91
H2-03 Multi-func-
tion output
2: terminal
26.
T
erminal 26 Sel
0 to 37
2 NO B B B B 6-91
Parameter Lists Chapter
7