D Digital Outputs List
Setting
l
Control mode
Page
g
value
V/f V/f
w/PG
Open loop
Vector
Flux
vector
g
0 During run 1 OK OK OK OK 6-92
1 Excitation OK OK OK OK 6-92
2 Frequency (ref/out) agree 1: detection width
L4-02
OK OK OK OK 6-104
3 Desired frequency (ref/setting) agree 1 (ON:
Output frequency = ±L4-01, detection width
L4-02)
OK OK OK OK 6-104
4 Frequency detection 1 (ON: +L4-01+output
frequency+–L4-01, detection width L4-02)
OK OK OK OK 6-104
5 Frequency detection 2
(ON: Output frequency++L4-01 or output
frequency)–L4-01, detection width L4-02)
OK OK OK OK 6-104
6 Inverter operation ready
READY: After initialization, no faults
OK OK OK OK ---
7 During DC bus low voltage (UV) detection OK OK OK OK ---
8 During baseblock 1 (ON: during baseblock) OK OK OK OK ---
9 Operation reference (ON: Operator) OK OK OK OK ---
A Run command remote operation (ON: Operator) OK OK OK OK ---
B Overtorque detection 1 NO (contact a: ON,
overtorque detection)
OK OK OK OK 6-108
C Loss of frequency reference (Effective when
operation selection is “1” for L4-05 frequency
reference missing)
OK OK OK OK 6-105
D DB overheat (ON: Resistance overheat or braking
Tr fault)
OK OK OK OK ---
E Fault (ON: Faults other than CPF00, CPF01 have
occurred.)
OK OK OK OK 8-1
F Not used. Do not set. --- --- --- --- ---
10 Minor fault (ON:Report displayed) OK OK OK OK 8-8
11 Fault reset command active OK OK OK OK ---
12 Timer output OK OK OK OK 6-46
13 Frequency (ref/out) agree 2 (Detection width:
L4-04)
OK OK OK OK 6-104
14 Desired frequency (ref/setting) agree 2 (ON:
Output frequency = L4-03, detection width L4-04)
OK OK OK OK 6-104
15 Frequency detection 3 (ON: output frequency
)–L4-03, detection width L4-04)
OK OK OK OK 6-104
16 Frequency detection 4 (ON: output frequency
+–L4-03, detection width L4-04)
OK OK OK OK 6-104
17 Overtorque detection 1 NC (Contact b: OFF,
torque detection)
OK OK OK OK 6-108
18 Overtorque detection 2 NO (Contact a: ON,
torque detection)
OK OK OK OK 6-108
19 Overtorque detection 2 NC (Contact b: OFF,
torque detection)
OK OK OK OK 6-108
1A During reverse run (ON: during reverse run) OK OK OK OK ---
Parameter Lists Chapter