7-53
Para
meter
No.
PageControl
mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
DescriptionNamePara
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
o2-02
Stop Key
Sets the Stop Key in the run
mode.
0:
Disabled (When the run
0, 1
1 NO B B B B 6-112
Oper Stop
Key
command is issued from
and external terminal, the
Stop Key is disabled.)
1:
Enabled (Ef
fective even
during run.)
o2-03
User
parameter
initial val
-
ues
Clears or stores user initial
values.
0:
Stores/not set
1:
Begins storing (Records the
set parameters as user
initial values.)
2:
All clear (Clears all
recorded user initial values)
0 to 2
0 NO B B B B 6-112
User De-
faults
recor
Note:
When the set parameters
are recorded as user ini
-
tial values, 1
1
10 will be
displayed in the Initialize
mode (A1-03.)
o2-04
Inverter ca-
pacity
selection
Do not set
Note:
This parameter is set by
the manufacturer
0 to FF
(See
note.)
0 (See
note.)
NO B B B B 6-113
Inverter
Model #
o2-05
Frequency
reference
setting
method
When the frequency reference
is set on the Digital Operator
’s
frequency reference monitor
,
sets whether the Enter Key is
necessary.
0:
Enter Key needed
0, 1
0 NO A A A A 6-113
Operator
M.O.P.
Note:
When set to 1, the Invert
-
er accepts the frequency
reference without Enter
Key operation.
o2-06
Operation
selection
when Digi
-
tal Operator
is discon-
nected
Sets the operation when the
Digital Operator is
disconnected.
0:
Disabled (Operation
continues even if the Digital
Operator is disconnected.)
1:
Enabled (OPR is detected
0, 1
0 NO A A A A 6-113
Oper
Detection
at
perator
disconnection. Inverter
output is cut of
f, and fault
contact is operated.)
o2-07
Cumulative
operation
time setting
Sets the cumulative operation
time in hour units.
Note:
Operation time is calcu
-
0
to
65535
0 NO A A A A 6-113
Elapsed
Time
Set
lated from the set values.
o2-08
Cumulative
operation
time selec-
tion
0:
Cumulative time when the
Inverter power is on. (All
time while the Inverter
power is on is
accumulated.
0, 1
0 NO A A A A 6-113
Elapsed
T
ime Run
1:
Cumulative Inverter run
time. (Only Inverter output
time is accumulated.)
Parameter Lists Chapter
7