8-7
Fault Display Probable causes and remediesMeaning
BUS
Option Com Err
CompoBus/D communications
error.
Communications error
occurred in the CompoBus/D
Communications Card.
Communications cable was broken, short-cir-
cuited, or wired incorrectly.
Check wiring of communications cables and
correct the fault.
Hardware on the Master end is faulty.
Check the Master and take necessary mea-
sures.
Data was damaged due to noise.
Change to special communications cables or
shielded cables and ground the shields on the
Master end or power supply end.
Separate communications cables from other
lines
and install a noise filter on the power sup
-
ply.
The Optional Card was damaged.
If wiring is correct and if the problem persists,
replace the Optional Card.
CPF00
COM-ERR (OP&INV)
Communications with the
Operator were not established
within 5 seconds after the
power was turned on.
The Digital Operator’s connector isn’t connected
properly.
Disconnect the Digital Operator and then con-
nect it again.
The Inverter CPU’s peripheral element is faulty.
Replace the Inverter.
CPF01
COM-ERR (OP&INV)
After communications were
established, there was a
transmission error with the
Digital Operator for more than
2 seconds.
The Digital Operator isn’t connected properly.
Disconnect the Digital Operator and then con-
nect it again.
The Inverter CPU’s peripheral element is faulty.
Replace the Inverter.
CPF02
BB Circuit Err
Baseblock circuit error Try turning the power supply off and on again.
The control circuit is damaged.
Replace the Inverter.
CPF03
EEPROM Error
EEPROM error Try turning the power supply off and on again.
The control circuit is damaged.
Replace the Inverter.
CPF04
Internal A/D Err
CPU internal A/D converter
error
Try turning the power supply off and on again.
The control circuit is damaged.
Replace the Inverter.
CPF05
External A/D Err
CPU external A/D converter
error
Try turning the power supply off and on again.
The control circuit is damaged.
Replace the Inverter.
Maintenance Operations Chapter
8

Table of Contents