8-6
Fault Display Probable causes and remediesMeaning
OPR
Oper Disconnect
Faulty Digital Operator
connection.
The Digital Operator
connection was broken during
Inverter operation. Detected
when the parameter is set as
follows: 02-06=1.
• Wiring cable is broken.
• The
Digital Operator or Inverter
contacts are faulty
.
→ After disconnecting the connectors and then
connecting
them again or cleaning the connec
-
tors, restart the power supply.
• Parameter was set incorrectly.
→ Set 02-06 to 0.
• If the problem persists, replace the cables or
Inverter.
EFO
Opt External Flt
External fault
(Communications/option)
• An
external fault was
input from an Optional Com
-
munications Card.
→ Reset
the external fault from the Optional
Com
-
munications Card.
→ Remove the cause of the external fault input.
EF3
External Fault 3
External fault (Input terminal 3)
• An
external fault was input from a multi-function in
-
put.
EF4 External fault (Input terminal 4)
EF5 External fault (Input terminal 5)
inputs.
EF6 External fault (Input terminal 6)
→ Remove the cause of the external fault.
EF7 External fault (Input terminal 7)
.
EF8 External fault (Input terminal 8)
E-15
SI-F/G Com Err
SYSMAC BUS
communications error.
An error occurred in the
SYSMAC BUS
communications line,
disrupting communications.
• The communications line was broken, short-cir-
cuited, or wired in reverse.
→ Check
the communications line
and correct the
trouble.
• Hardware on the Master end is faulty.
→ Check the Master and take necessary mea-
sures.
• Communications
data was damaged due to noise.
→ Use twisted-pair cables for communications
lines and ground all the shields on the Master
end.
• The Optional Card was damaged.
→ If wiring is correct and if the problem persists,
replace the Optional Card.
Maintenance Operations Chapter