9-18
D Digital Operator Connecting Cable
3G3FV-PCN25
This
is a special cable for the 3G3FV Series. It is used for connecting the Inverter to the Digital Operator
.
The cable length can be either 1 or 3 meters.
D Standard Models
3G3FV-PCN125 Cable length: 1 meter
3G3FV-PCN325 Cable length: 3 meters
D DC Reactor (Yaskawa Electric)
3G3HV-PUZDABAMH
This
DC Reactor is used for controlling harmonic current generated by the Inverter
. It is more ef
fective
than
an AC reactor
, and can be used in conjunction. It is intended for use with Inverters of 15 kW or less.
(It is built into Inverters of 18.5 kW and over.)
D Standard Models
Inverter DC Reactor
Voltage
class
Maximum
applicable
motor
capacity
(kW)
3G3IV-PUZDAB Rated
voltage (V)
Rated
current (A)
Inductance
(mH)
Loss (W)
200-V
l
0.4/0.75 5.4A8MH
800 VDC
5.4 8 8
class
1.5 to 3.7 18A3MH 18 3 18
5.5/7.5 36A1MH 36 1 22
11/15 72A0.5MH 72 0.5 29
400-V
l
0.4/0.75 3.2A28MH
800 VDC
3.2 28 9
class
1.5/2.2 5.7A11MH 5.7 11 11
3.7 12A6.3MH 12 6.3 16
5.5/7.5 23A3.6MH 23 3.6 27
11/15 33A1.9MH 33 1.9 26