3-7
H Parameter Setting Levels (Partial)
Application b1 Sequence b1-01 Reference source
b1-03 Stopping method
C1-01 Accel T
ime 1
C1 Accel/Decel
C2 S-Curve Acc/Dec
Tuning
Reference
Parameter to be changed
[Mode] [Group] [Function] [Parameter]
Operation mode
Initialize mode
Program mode
MENU
b1-02 Run source
C1-02 Decel T
ime 1
H Setting the Parameter in the Quick-start Access Level
The parameter level will be displayed when the Enter Key is pressed at the program mode display.
Key sequence Display Explanation
** Main Menu **
Operation
Displays operation mode.
2 times
** Main Menu **
Programming
Displays program mode.
Reference Source
Terminals
Puts the Unit in program mode.
Displays the b1-01 Reference source selection.
Run Source
Terminals
Displays the b1-02 Run source selection.
Stopping Method
Ramp to Stop
Displays the b1-03 Stopping method selection.
Accel Time 1
c1-01= 10.0 Sec
Displays C1-01 Acceleration time 1.
Accel Time 1
0010.0 Sec
Selects the parameter so that the leading 0 flashes.
(The digit that can be changed flashes.)
2 times
Accel Time 1
0010.0 Sec
Moves the cursor so that the “1” digit flashes.
Accel Time 1
0020.0 Sec
Changes the 1 to a 2.
Entry Accepted
Writes the new setting.
--- Accel Time 1
c1-01= 20.0 Sec
Returns to the C1-01 Acceleration time 1 display.
** Main Menu **
Programming
Returns to the program mode display.
Preparing for Operation Chapter
3