3-14
Item Valid
access levels
Min.
Units
Output signal
levels for
multi-function
analog outputs
FunctionDisplayItem
Flux
Vec-
tor
Open
Vec-
tor
V/f
w/PG
V/f
Min.
Units
Output signal
levels for
multi-function
analog outputs
FunctionDisplay
U1-25
DI-16 Reference
Monitors the reference value from a
3G3FV
-PDI16H2 Digital Command Card.
The value will be displayed in binary or
BCD depending on parameter F3-01.
Can’t be output.
--- A A A A
U1-26 V
oltage Ref (Vq)
Monitors the Inverter
’
s internal voltage
reference value for the motor
’s secon-
dary current control.
10 V
: 200 (400) V
AC
(0 to
±
10 V possible)
0.1 V
X X A A
U1-27 V
oltage Ref (Vd)
Monitors the Inverter
’
s internal voltage
reference value for the motor
’
s excitation
current control.
10 V
: 200 (400) V
AC
(0 to
±
10 V possible)
0.1 V
X X A A
U1-28 CPU ID Manufacturer’s CPU software ID number
Can’t be output.
0.1 V
A A A A
U1-32 ACR(q) Output Monitor’
s the current control output value
for the motor
’s secondary current.
10 V
: 100%
0.1% X X A A
U1-33 ACR(d) Output Monitor’
s the current control output value
for the motor
’
s excitation current.
10 V
: 100%
0.1% X X A A
U1-34 OPE Detected
Displays the first constant number for
which an OPE error was detected.
Can’t be output.
--- A A A A
U1-35
Zero Servo Pulse
Multiplies the number of PG pulses by
four to display the movement width at the
zero servo stop point.
Can’t be output.
1 X X X A
U1-36
PID Input
PID reference + PID reference bias – PID
feedback value
The max. frequency corresponds to
100%.
10 V
:
Max. frequency
0.01
%
A A A A
U1-37
PID Output
PID control output
The max. frequency corresponds to
100%.
10 V
:
Max. frequency
0.01
%
A A A A
U1-38
PID Setpoint
PID reference + PID reference bias
The max. frequency corresponds to
100%.
10 V
:
Max. frequency
0.01
%
A A A A
Preparing for Operation Chapter