3-13
Item Valid
access levels
Min.
Units
Output signal
levels for
multi-function
analog outputs
FunctionDisplayItem
Flux
Vec-
tor
Open
Vec-
tor
V/f
w/PG
V/f
Min.
Units
Output signal
levels for
multi-function
analog outputs
FunctionDisplay
U1-11
Output T
erm Sts
(Output terminal
status)
Shows the ON/OFF status of outputs.
U1-11=00000000
1: T
erminals 9–10 ON
1: T
erminal 25 ON
1: T
erminal 26 ON
Not used. (always 0)
1: T
erminals 18/19–20
ON
Can’t be output.
--- Q Q Q Q
U1-12
Int Ctl Sts 1
(Internal control
status)
Shows the Inverter
’
s operating status.
U1-12=00000000
1: Running
1: Zero-speed level
1: Reverse
1: Reset input ON
1: F
.ref/F
.out agree
1: Inverter ready
1: Minor fault detected
1: Major fault detected
Can’t be output.
--- Q Q Q Q
U1-13
Elapsed T
ime
Monitors the Inverter
’
s elapsed operating
time.
The initial value and running/power-on
time selection can be set with parameters
o2-07 and o2-08.
Can’t be output.
1 hr
Q Q Q Q
U1-14 FLASH ID Manufacturer’
s ID number
Can’t be output.
--- Q Q Q Q
U1-15 T
erm 13 Level
(T
erminal 13 input
voltage level)
Monitors the input voltage of the frequen
-
cy reference (voltage).
An input of 10 V corresponds to 100%.
10 V: 100% (10 V)
(0 to
±
10 V possible)
0.1% B B B B
U1-16 T
erm 14 Level
(T
erminal 14 input
current level)
Monitors the input current of the frequen
-
cy reference (current).
An input of 20 mA corresponds to 100%.
10 V: 100% (20 mA)
(0 to +10 V output)
0.1% B B B B
U1-17 T
erm 16 Level
(T
erminal 16 input
voltage level)
Monitors the input voltage of the multi-
function analog input.
An input of 10 V corresponds to 100%.
10 V: 100% (10 V)
(0 to
±
10 V possible)
0.1% B B B B
U1-18
Mot SEC Current
Monitors the calculated value of the mo
-
tor’
s secondary current (Iq). The motor
’s
rated current corresponds to 100%.
10 V
: Rated current
(0 to +10 V output)
0.1% B B B B
U1-19
Mot EXC Current
Monitors the calculated value of the mo
-
tor’
s excitation current (Id). The motor
’s
rated current corresponds to 100%.
10 V
: Rated current
(0 to +10 V output)
0.1% X X B B
U1-20
SFS Output
Monitors the output frequency after a soft
start. The display shows the frequency
without the correction from compensation
functions such as slip compensation.
10 V
:
Max. frequency
(0 to
±
10 V possible)
0.01
Hz
A A A A
U1-21
ASR Input
Monitors the input to the speed control
loop. The max. frequency corresponds to
100%.
10 V
:
Max. frequency
(0 to
±
10 V possible)
0.01
%
X A X A
U1-22
ASR Output
Monitors the output from the speed con
-
trol loop. The motor
’
s rated current corre
-
sponds to 100%.
10 V
: Rated current
(0 to
±
10 V possible)
0.01
%
X A X A
U1-23
Speed Deviation
Monitors the speed deviation within the
speed control loop. The max. frequency
corresponds to 100%.
10 V
:
Max. frequency
(0 to
±
10 V possible)
0.01
%
X A X A
U1-24 PID Feedback
Monitors the feedback value when PID
control is used. The input for the max.
frequency corresponds to 100%.
10 V
:
Max. frequency
(0 to
±
10 V possible)
0.01
%
A A A A
Preparing for Operation Chapter
3