Setting Mode Setting Using Configuration Password
Event Message Editable Default Event Class
W70XX:EDP Error Warning
W42XX:Setpoint Warning
W43XX:Fill Value Too Low Warning
W55XX:Sequence check Warning
W40XX:Filing Stopped Warning
W41XX:Filling Aborted Warning
W44XX:Overfill Warning
W45XX:Out of Tolerance Warning
W56XX:Scale not permitted Warning
W46XX:Weight Invalid Warning
A48XX:Analog Interface Cable Breakage Alarm
M18XX:Balance or No. of Dumps over 95% Message
M52XX:Function not accessible Message
M53XX:Weighing Aborted Message
A65XX:ICP communication error Alarm
W54XX:No load check Warning
Operating Sequence
Start function to access the list of editable event messages (see Table above):
W01XX:Timeout
Event Class
Warning
The upper line shows the event message to be edited; the lower, a scroll field, for you
to select from possible event classes.
Operate [ENTER] key to go to the event message whose class you wish to change.
Use DIRECTION KEYS to select new event class and acknowledge with [ENTER]
key.
Next listed event is output. If no further editing is required, exit function with [OK] key.
New event class is displayed when the event reoccurs for the first time.
5.3.2.9 Fct. 435:Calibrate Analog Output
Use menu item to calibrate analog output, or reset its previous calibration. This helps
you to match the analog signal range to the requirements of the matching station.
To be able to use analog output, DISOMAT must be equipped with the
VEA400V option (no standard feature).
Connect matching station via XAE on p.c. board VNT400V.
Before performing calibration, connect ammeter to connector XAE (VNT400V).
As analog signal, one of multiple value variables (weight, balance, ...) can be selected.
The DISOMAT analog output signal is set in steps of 10 000 from smallest to highest
value of selected variable.
A 'step' in the analog signal does not necessarily change display of weight value; its
resolution is independent of the number of scale increments.
BV-H2313 GB 0630 DISOMAT
®
Opus – Operating Manual
- 70 - © Schenck Process GmbH, Darmstadt