Connection to the PROFIBUS fieldbus
PROFIBUS is an asynchronous serial fieldbus. As a rule, all subscribers are connected
in a line (line topology). With its BUS IN and BUS OUT connections, the fieldbus module
serves as a T-connector to the MLG-2. The MLG-2 is connected to the fieldbus with a
stub cable. If replacement is necessary, the terminator (part number 6021156) must
be supplemented (MLG-1 has an internal resistor).
The bus cables must satisfy the characteristics for cable type A according to IEC
61156:
Two-wire, twisted and shielded
Impedance: 135 … 165 Ωat 3 … 20MHz
Capacitance: <30pF/m 
Resistance: <110 Ω/km 
Wire cross-section: >0.34mm
2
Wire diameter: >0.64mm
NOTE
Do not mix up the two PROFIBUS A and PROFIBUS B High data cables in the same
segment.
Connect a large area of the shielding to protective ground at both ends of the
cable.
We recommend using preassembled connection cables for the wiring (see "Accesso‐
ries", page 170.
T-connector for connecting the sender and fieldbus module
A T-splitter is available for the MLG-2, which connects the sender and fieldbus module
with each other and also provides the connection options for the power supply, switch‐
ing output 1 and the test input.