Installation and Commissioning
8-24 7SA6 Manual
C53000-G1176-C133-1
1
) Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2
) Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115 VAC
The jumpers X71, X72 and X73 on the input/output board C–I/O–1 are for setting the
bus address and must not be changed. Tables 8-11 and 8-12 list the jumper
presettings.
Figures 8-8 to 8-10 show the mounting location of the printed circuit boards.
Table 8-10 Jumper setting of control voltages of binary inputs BI6 to BI29 on the binary in-
put/output boards C– I/O–1 for housing size
1
/
1
Binary input
Jumper
Threshold
17 V
1
)
Threshold
73 V
2
)
Slot 33
left
Slot 19
right
Slot 19
left
BI6 BI14 BI22 X21/X22 L M
BI7 BI15 BI23 X23/X24 L M
BI8 BI16 BI24 X25/X26 L M
BI9 BI17 BI25 X27/X28 L M
BI10 BI18 BI26 X29/X30 L M
BI11 BI19 BI27 X31/X32 L M
BI12 BI20 BI28 X33/X34 L M
BI13 BI21 BI29 X35/X36 L M
Table 8-11 Jumper setting of printed circuit board addresses of binary input/output
boards C-I/O-1 for housing size
1
/
2
Jumper Mounting
location
Slot 19
X71 H
X72 L
X73 H
Table 8-12 Jumper setting of printed circuit board addresses of binary input/output
boards C-I/O-1 for housing size
1
/
1
Jumper Mounting location
Slot 19 left Slot 19 right Slot 33 left
X71 H L H
X72 H H L
X73HHH