6-20
Table 6-15 describes the Points associated with the Analog Pseudo Card (System
Address 30).
Table 6-15. Analog Pseudo Card (System Address 30)
Point Number: Description Device Type Point Type Purpose
1: Fire Alarm Count Analog Pseudo Analog Indicates the current number of
fire alarms in the system.
2: Supervisory Count Analog Pseudo Analog Indicates the current number of
supervisories in the system.
3: Trouble Count Analog Pseudo Analog Indicates the current number of
troubles in the system
4: System Startup Analog Pseudo Analog Turns on for one poll cycle at
system startup for user specific
initialization needs
5-25: User Definable Analog Pseudo Analog Open for specific job needs and
requirements
Table 6-16 describes the Points associated with the List Pseudo Card (System
Address 31).
Table 6-16. List Pseudo Card (System Address 31)
Point Number Description Device Type Point Type Purpose
1: System Monitors and Manual
Evacuation
List Pseudo List Contains all monitor zones and
the manual evacuation pseudo
point (not user editable)
2: Waterflow Monitors List Pseudo List Contains all waterflow monitors
(not user editable)
3: Sprinkler Monitors List Pseudo List Contains all sprinkler monitors
(not user editable)
4: Primary Elevator Capture
Monitors
List Pseudo List User editable list for placing
primary elevator capture monitor
zones into
5: Alternate Elevator Capture
Monitors
List Pseudo List User editable list for placing
alternate elevator capture monitor
zones into
6: Points Off with Silence List Pseudo List User editable list for placing
points which should be turned off
with a signal silence operation
7: Points Off with Reset List Pseudo List User editable list for placing
points which should be turned off
with a successful system reset
8-25: User Definable List Pseudo List Open for specific job needs and
requirements