6-19
Table 6-14 describes the Points associated with the Digital Pseudo Card (System
Address 29).
Table 6-14. Digital Pseudo Card (System Address 29)
Point Number Description Device Type Point Type Purpose
1: Unacked Fire in System Digital Pseudo Utility Indicates an unacknowledged fire
alarm exists in the system.
2: Unacked Supervisory in System Digital Pseudo Utility Indicates an unacknowledged
supervisory exists in the system.
3: Unacked Trouble in System Digital Pseudo Utility Indicates an unacknowledged
trouble exists in the system.
4: Extra RUI Card in System Digital Pseudo Trouble Indicates RUI card that is not
configured is responding.
5: Extra I/O Card in System Digital Pseudo Trouble Indicates I/O card that is not
configured is responding.
6: RUI Communication Trouble Digital Pseudo Trouble Annunciates RUI short circuit.
7: User SMPL Program Control Digital Pseudo Utility Turns on/off user SMPL program
8: Cold Start Digital Pseudo Trouble Indicates cold restart of panel.
9: Warm Start Digital Pseudo Trouble Indicates warm restart of panel.
10: Manual Evacuation Digital Pseudo Fire Indicates manual evacuation
condition.
11: Time/Date Incorrect Digital Pseudo Trouble Indicates time/date is not set.
12: Simplex Service Mode Digital Pseudo Trouble Simplex service mode (level 4)
13: Keypad Inactivity Disable Digital Pseudo Utility Disables keyboard inactivity timer
14: Active List Overflow Digital Pseudo Trouble Indicates one of the active lists has
overflowed, system events lost.
15: Low Battery Digital Pseudo Trouble Annunciates low battery trouble
16: City Circuit Disconnect Digital Pseudo Trouble Indicates city circuit disconnect
trouble
17: City Circuit 1/DACT Trouble Digital Pseudo Trouble Indicates city circuit 1/DACT
supervision trouble
18: City Circuit 2 Trouble Digital Pseudo Trouble Indicates city circuit 2 supervision
trouble
19: Expansion Power Supply Failure Digital Pseudo Trouble Indicates expansion power supply
status
20: Control Point Bypass Digital Pseudo Trouble Indicates control point bypass
trouble
21: Elevator Bypass Digital Pseudo Trouble Indicates elevator bypass trouble
22: Doorholder Bypass Digital Pseudo Trouble Indicates doorholder bypass
trouble
23: Verification Tally Limit Exceeded Digital Pseudo Trouble Indicates verification tally limit has
been exceeded on a system
verification monitor
24: Degraded Battery Digital Pseudo Trouble Indicates battery degraded trouble
25: Battery Charger Digital Pseudo Trouble Indicates battery charger trouble
26: Walktest Active Digital Pseudo Trouble Indicates Walk Test active trouble
27-50: User Definable Digital Pseudo Utility Open for specific job needs and
requirements
Continued on next page
Reference Information, Continued
Digital Pseudo Card