2-23
The Active Point Reminder sounds the piezo on the panel for five seconds eight
hours after a trouble is acknowledged. This serves as a reminder that there is still
a trouble in the system. To turn the Active Point Reminder ON or OFF for the
4005, use the following steps:
1. Follow Steps 1 through 3 under Editing a Point Label.
2. Press <Next> or <Previous> to scroll through the menus until
[
6\VWHP2SWLRQV] is displayed (A) and then press <Enter>.
A.
B.
C.
D.
Figure 2-21. Typical Screens Used to Turn
the Active Point ON or OFF
3. Press <Next> or <Previous> until [
$FWLYH3RLQW5HPLQGHU] is
displayed (B) and then press <Enter>.
The focus brackets ( [ ] ) appear in the New: field (C)of the display.
4. Press <Next> or <Previous> to choose ON or OFF for the reminder and
then press <Enter>.
5. Press <Enter> to confirm your selection or Exit to cancel (D).
Option is updated is displayed when selecting Enter.
Active Point Reminder
Turning the Active Point
Reminder ON or OFF
),5(  683(59,625< 7528%/( 
3URJUDPPLQJ>6\VWHP2SWLRQV@
),5(  683(59,625< 7528%/( 
6\VWHP2SWLRQV>$FWLYH3RLQW5HPLQGHU@
$FWLYH3RLQW5HPLQGHU
1HZ>2))@ &XUUHQW2))
3UHVV(17(5WRFRQILUP(;,7WRFDQFHO
&DUG7\SH >6&8&DUG@
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4005 and is the answer not in the manual?

Simplex 4005 Specifications

General IconGeneral
BrandSimplex
Power Supply24 VDC
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
CompatibilityCompatible with Simplex fire alarm control panels

Related product manuals