2-24
The Silence/Reset Inhibit timer ignores the keypress of the Silence and Reset
Keys for a specified time (0-60 mins.). To set the Silence/Reset Inhibit timer in
minutes for the 4005, use the following steps:
1. Follow Steps 1 through 3 under Editing a Point Label.
2. Press <Next> or <Previous> to scroll through the menus until
[
6\VWHP2SWLRQV] is displayed (A) and then press <Enter>.
A.
B.
C.
D.
Figure 2-22. Typical Screens Used to Set the
Silence/Reset Inhibit Timer
3. Press <Next> or <Previous> until [6LOHQFH5HVHW,QKLELW] is
displayed (B) and then press <Enter>.
The focus brackets ( [ ] ) appear in the New: field (C) of the display.
4. Press <Next> or <Previous> to choose the duration (1-60 minutes) for the
inhibit timer and then press <Enter>.
Note: When initially setting a value for a System Option, all values in
the ‘New:’ field reflect the Current: field’s setting. A value of 00 is
a disabled state of that System Option (for example, 00 Mins
means that the Alarm Silence/System Reset Timer Inhibit is not
active).
5. Press <Enter> to confirm your selection or Exit to cancel (D).
“Option is updated” is displayed when selecting Enter.
Silence/Reset Inhibit Timer
Setting the Silence/Reset
Inhibit Timer
),5( 683(59,625< 7528%/(
3URJUDPPLQJ>6\VWHP2SWLRQV@
),5( 683(59,625< 7528%/(
6\VWHP2SWLRQV>6LOHQFH5HVHW,QKLELW@
$ODUP6LOHQFH6\VWHP5HVHW7LPHU,QKLELW
1HZ>@ &XUUHQW0LQV
3UHVV(17(5WRFRQILUP(;,7WRFDQFHO
1HZ>@ &XUUHQW0LQV
Technical Manuals Online! - http://www.tech-man.com