2-27
The Door Drop AC Loss is specified time (0-60 min.) that doors are held open
on an AC loss. To set the Door Holder AC Fail Drop Timer in minutes for the
4005, use the following steps:
1. Follow Steps 1 through 3 under Editing a Point Label.
2. Press <Next> or <Previous> to scroll through the menus until
[
6\VWHP2SWLRQV] is displayed (A) and then press <Enter>.
A.
B.
C.
D.
Figure 2-25. Typical Screens Used to Set the
Door Drop AC Loss Timer
3. Press <Next> or <Previous> until [
'RRU'URS$&/RVV] is displayed
(B) and then press <Enter>.
The focus brackets ( [ ] ) appear in the New: field (C) of the display.
4. Press <Next> or <Previous> to choose the duration (1-60 minutes) for the
AC fail drop timer and then press <Enter>.
Note: When initially setting a value for a System Option, all values in
the New: field will reflect the Current: field's setting. A value of
00 is considered a disabled state of that System Option (for
example, 00 Mins means that the Door Holder - AC Fail Drop
Timer is not active).
5. Press <Enter> to confirm your selection or Exit to cancel (D). Option is
updated is displayed when selecting Enter.
Door Drop AC Loss Timer
Setting the Door Drop AC
Loss Timer
),5(  683(59,625< 7528%/( 
3URJUDPPLQJ>6\VWHP2SWLRQV@
),5(  683(59,625< 7528%/( 
6\VWHP2SWLRQV>'RRU'URS$&/RVV@
'RRU+ROGHU²$&)DLO'URS7LPHU
1HZ>@ &XUUHQW0LQV
3UHVV(17(5WRFRQILUP(;,7WRFDQFHO
1HZ>@ &XUUHQW0LQV
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4005 and is the answer not in the manual?

Simplex 4005 Specifications

General IconGeneral
BrandSimplex
Power Supply24 VDC
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
CompatibilityCompatible with Simplex fire alarm control panels

Related product manuals