4-4
In the following example any activated initiating device (e.g., smoke detectors
and pull stations) on a particular floor energizes the signals (e.g., horns) on that
floor, the floor above that floor, and the floor below that floor. Signals sound
steady until silenced by the alarm silence key.
1) Edit a NAC/Relay card and assign NAC circuits as Signal points (see the
Edit Card, Modify I/O Card Devices section of this publication).
2) Change the point types (see the Edit Points, Edit Point Type section of
this publication).
3) Change the custom labels of the points (see the Edit Points, Edit Point
Label section of this publication).
4) Add the signals to the "Control Points, OFF with Silence" List 31-06 (see
the Lists, Add Points to a List section of this publication).
5) Add the following SMPL equations (see the To Start SMPL Programming
section of this publication):
Selective Signal - Equation 1 (Fire Floor Above, Floor Below)
Equation Point Label Point Type
$1<),5('(7 VW)ORRU(DVW:LQJ=RQHV
(QGRI,QSXW
+2/'3UL VW)ORRU(DVW:LQJ6LJ 6LJQDO
+2/'3UL QG)ORRU(DVW:LQJ6LJ 6LJQDO
(QGRI2XWSXW
Selective Signal - Equation 2 (Fire Floor Above, Floor Below)
Equation Point Label Point Type
$1<),5('(7 QG)ORRU(DVW:LQJ=RQHV
(QGRI,QSXW
+2/'3UL QG)ORRU(DVW:LQJ6LJ 6LJQDO
+2/'3UL UG)ORRU(DVW:LQJ6LJ 6LJQDO
+2/'3UL VW)ORRU(DVW:LQJ6LJ 6LJQDO
(QGRI2XWSXW
Selective Signal - Equation 3 (Fire Floor Above, Floor Below)
Equation Point Label Point Type
$1<),5('(7 UG)ORRU(DVW:LQJ=RQHV
(QGRI,QSXW
+2/'3UL UG)ORRU(DVW:LQJ6LJ 6LJQDO
+2/'3UL WK)ORRU(DVW:LQJ6LJ 6LJQDO
+2/'3UL QG)ORRU(DVW:LQJ6LJ 6LJQDO
(QGRI2XWSXW
Continued on next page
SMPL Language Applications, Continued
Selective Signal Operation for
Fire Floor, Floor Above, and
Floor Below
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4005 and is the answer not in the manual?

Simplex 4005 Specifications

General IconGeneral
BrandSimplex
Power Supply24 VDC
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
CompatibilityCompatible with Simplex fire alarm control panels

Related product manuals