6-5
The Edit SMPL function has the following parameters:
Max. number of Equations: 40
Max. number of Statements (Input or Output combined) per Equation: 6
01: Input Side
ALARM 18-01
OR DETECT 18-04
End of Input
HOLD ON 20-01 PRI 9,9
End of Output
02: Input Side
ON 28-01
End of Input
HOLD OFF 20-01 PRI 9,9
End of Output
Tables 6-2 through 6-4 show valid operator codes that are supported from front
panel programming.
Table 6-2. SMPL Input Qualifiers Table
OPCODE (Qualifier) DESCRIPTION
FIRE DET Fire Detect State
FIRE Fire State
FIRE ACK Fire Acknowledge State
SUPV Supervisory State
SUPV ACK Supervisory Acknowledge State
TBL Trouble State
TBL ACK Trouble Acknowledge State
ON/CODE Oncoding State
COMP CNST Compare to a constant value
OFF Off State
ANY Any Number of elements in a List
ALL All element in a List
DELAY CNST Delay for a constant value
Table 6-3. SMPL Input Operators Table
OPCODE MNEMONIC DESCRIPTION
29 NOT NOT operator
31 AND AND operator
30 OR OR operator
Continued on next page
SMPL Programming
Edit SMPL
Sample Program
Valid Operator Codes and
Parameter Tables
(where 18 is the card address number
and 01/ 04 is the point number)
(where 9,9 indicates the points set
and reset priorities respectively)
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4005 and is the answer not in the manual?

Simplex 4005 Specifications

General IconGeneral
BrandSimplex
Power Supply24 VDC
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
CompatibilityCompatible with Simplex fire alarm control panels

Related product manuals