6-10
Table 6-5 shows each System Option, the valid values (ranges) and the default
value for the option.
Table 6-5. System Options Chart
Option Name Value or Range Default Value
Time/Date Format
• 12-Hour
• 24-Hour
12-Hour
Active Point Reminder
(ALM, SUPV, TBL)
sounds every 8 hours
• YES
• NO
NO
Alarm Silence/Reset
Inhibit Timer
• 0 – 60 minutes
0
Alarm Signal Cutout
Time
• 0 – 60 minutes
0 with no cutout
Doorholder drop on
Alarm
• 0 – 60 seconds
0
Doorholder drop on
AC loss
• 0 – 60 minutes
5 minutes
Audible Signal
Operation
• Steady
• Slow March Time
• Fast March Time
• Temporal
Steady
Visible Signal
Operation
• Steady
• Slow March Time
• Fast March Time
• Temporal
Steady
Enable City Circuit 1
• YES
• NO
NO
Enable City Circuit 2
• YES
• NO
NO
Expansion Power
Supply
• ON
• OFF
ON
Refer to the ‘Changing Access Level’ section of this document (Chapter 2) for
information regarding Access Levels.
Refer to the ‘Changing Passcodes’ section of this document (Chapter 2) for
information regarding Passcodes.
Refer to the ‘Canceling the Editing Changes’ section of this document
(Chapter 2) for information on the Restore CFIG option.
Refer to the ‘Saving Editing Changes’ section of this document (Chapter 2) for
information on the Save CFIG option.
System Options
System Option Chart
Edit Access Levels
Edit Passcodes
Restore CFIG (Clear Edit
Buffer)
Save to CFIG