EasyManua.ls Logo

Valtra 6550 - Implement Socket; Checking Line from Implement Socket to AC; Frequency Inputs; Digital Inputs

Valtra 6550
1361 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
379
Model Code Page
34. Autocontrol ---III
15. 6. 1992
6600E, 8100E 342 9
AC---III, implement socket
Implement sensors
Flow meter
RPM sensor
Piece counter
Working position
Signals for controlling
linear actuator
When the limit of count is reached
Checking line from implement socket to
A C --- I I I u n i t
--- Switch on current to the tractor
--- Measure the supply voltage between socket terminals 1
and 2 (= battery voltage, about 12 V DC).
--- Connect a microcomputer to the AC---III unit and activate
the trouble shooting chart (see page 341/1).
FREQUENCY INPUTS
1. Shunt between socket terminals 2 and 4 (break connec-
tion). A number signal must appear on the PC at point Flow.
This function is the same as the flow meter paddle wheel
would revolve. Also AC---III display shows some value in the
liquid amount mode (litres).
2. Shunt between socket terminals 2 and 5 (break connec-
tion). A number signal must appear on the PC at point RPM
impl. Also AC---III display shows some value in the implement
RPM mode. This function is the same as a magnet would
pass by the sensor.
3. Shunt between socket terminals 2 and 6. A number signal
must appear on the PC at point PCS every time the connec-
tion is broken off and on (summing counter). Also AC ---III dis-
play shows in the piece counter mode the same value. Note
possible limiting program, which limits the max number of
items. When the limit value is achieved a signal (0 changes
to 1) appears at the point Pieces counter (DIGITAL OUT-
PUTS). This signal can also be measured with a voltmeter
between socket terminals 2 and 10. This function is the same
as a magnet would pass by the sensor.
DIGITAL INPUTS
4. Activate the hydraulic power lift and turn the lift/lower switch
to the lowering position. Shunt between socket terminals
2and 9. A signal (1 changes to 0) appears on the PC at point
Implement pos. When the socket terminals are connected
the arrow on the AC---III display turns to point upwards. The
function is the same as a magnet would be opposite the sen-
sor. The lift/lower switch has the same function.
ANALOG INPUTS
5. Signal from possible position potentiometer: Shunt
between socket terminals 1 and 3, after which a number sig-
nal appears on the PC at the point Implement pot
. Here with
battery voltage the signal is about 250. Also AC---III display
shows some value (e.g. 100) in the implement position mode.
Signals to linear actuator
--- connect an adjustable resistor to the socket poles 1 (+:
black), 2 (---: Red) and 3 (sign: Yellow).
--- calibrate the resistor’s extreme positions (e.g. 0 (P1) and
100 (P2)).
--- input 5 pcs pre---programmed resistor positions (e.g. 10,
30, 50, 70 and 90)
--- move the resistor spindle inwards and outwards in the
middle range and check that the output signals appear on the
PC with e.g. the pre ---set position 50. Implement dir (current
to a relay for controlling actuator rotation direction; 0 or 1) and
Implement act (current to a relay for controlling actuator; 0
or 1) (both DIGITAL OUTPUTS)
By connecting a test lamp to the socket poles 7 or 8 (earth
from any frame contact) it can be checked if the current
actually comes to the socket.
N.B. If the line from the socket does not function, check con-
nectors X3C and X4C (in the lever console). Check also wire
connections in the socket. If the output signals do not come
the ECS is faulty.

Table of Contents

Related product manuals