TITANUS
MICRO·SENS
®
Technical Data
06/13
57
Detection box TITANUS
MICRO·SENS
®
Detection box
Power supply (Ue)
Nominal power supply
15 - 30 V DC
24 V DC
Power consumption at idle status 30 mA
Power consumption at alarm status
Device variant without smoke level
38 mA
Power consumption at alarm status
Device variant with smoke level
68 mA
Dimension (H x W x D mm) 70 x 140 x 222 mm
Weight 0.8 kg
Protection class (EN 60 529) IP 54
material plastic (ABS)
colour papyrus white, RAL 9018
Detection box
Deep freeze version
– 20° to +60°C
– 40° to +60°C
not condensed max. 95 % rf (without dew)
Operation
Fire alarm
Action alarm
Fault
Smoke level display
green operating display
red alarm display
red alarm display (optional)
yellow collective fault
yellow smoke level display 1 to 10
(10 segments) (optional)
Infrared interface IR
Transmitter / Receiver
4.2
Voltage
with Smoke level and
Processo
Dimensions
Weigh
Protection class
Housing
Temperature range
Humidit
Displays on device