In order to ensure a short transport time for the smoke fumes in the sampling
pipe and thus enable rapid detection, it is better to plan several shorter than
a few long ones (preferably a U- or double U-pipe system).
4 types of pipe designs can be selected, depending on the cabinet geometry
(see Figure „Project planning“).
I-pipe An air sampling smoke detection pipe system without branches.
U-pipe An air sampling smoke detection pipe system which branches into 2
air sampling branches after the connection to the TITANUS MI-
CRO·SENS
®
.
M-pipe An air sampling smoke detection pipe system which branches into 3
air sampling branches after the connection to the TITANUS MI-
CRO·SENS
®
.
Double-U-pipe An air sampling smoke detection pipe system which branches into 4
air sampling branches after the connection to the TITANUS MI-
CRO·SENS
®
.
NOTICE
The design for fire location should be the I-pipe configuration.
Branch length
Pipe designs