EasyManua.ls Logo

WAGNER Titanus Micro-Sens - Page 90

WAGNER Titanus Micro-Sens
238 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Design
TITANUS
MICRO·SENS
®
90
06/13
TIP
If the maximum distance is exceeded a correction by an additonal aspira-
tion aperture on a branch pipe can be done. In this connection please no-
tice that two aspiration apertures in total can be projected on each branch
pipe.
NOTICE
When the fire location (ROOM·IDENT) localization must only be one aspi-
ration aperture per branch pipe can are projected. At least 3m distance
must be maintained between the suction port of the first branch pipe and
each configured subsequent aspiration aperture.
Folgen

Table of Contents

Related product manuals