EasyManua.ls Logo

YASKAWA A1000 Series

YASKAWA A1000 Series
544 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.2 b: Application
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual 143
Parameter Details
5
b1-08: Run command selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being
used to adjust parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-
Tuning Mode). If required by the application, set b1-08 to allow the drive to run while in the Programming Mode.
Setting 0: Disabled
A Run command is not accepted while the digital operator is in the Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
Setting 0: Standard phase order
Setting 1: Switched phase order
b1-15: Frequency Reference Selection 2
Refer to b1-01: Frequency Reference Selection 1 on page 136.
b1-16: Run Command Selection 2
Refer to b1-02: Run Command Selection 1 on page 137.
b1-17: Run Command at Power Up
This parameter is used to determine whether an external Run command that is active during power up will start the drive
or not.
Setting 0: Run command at power up is not issued
The Run command has to be cycled to start the drive.
Note: For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is
issued at power up, the RUN indicator LED will flash quickly.
No. Parameter Name Setting Range Default
b1-08 Run Command Selection while in Programming Mode 0 to 2 0
No. Parameter Name Setting Range Default
b1-14 Phase Order Selection 0 or 1 0
No. Parameter Name Setting Range Default
b1-15 Frequency Reference Selection 2 0 to 4 0
No. Parameter Name Setting Range Default
b1-16 Run Command Selection 2 0 to 3 0
No. Parameter Name Setting Range Default
b1-17 Run Command at Power Up 0 or 1 0

Table of Contents

Other manuals for YASKAWA A1000 Series

Related product manuals