■ b1-08: Run command selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being
used to adjust parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-
Tuning Mode). If required by the application, set b1-08 to allow the drive to run while in the Programming Mode.
Setting 0: Disabled
A Run command is not accepted while the digital operator is in the Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
■
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
Setting 0: Standard phase order
Setting 1: Switched phase order
■ b1-15: Frequency Reference Selection 2
Refer to b1-01: Frequency Reference Selection 1 on page 136.
■
b1-16: Run Command Selection 2
Refer to b1-02: Run Command Selection 1 on page 137.
■
b1-17: Run Command at Power Up
This parameter is used to determine whether an external Run command that is active during power up will start the drive
or not.
Setting 0: Run command at power up is not issued
The Run command has to be cycled to start the drive.
Note: For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is
issued at power up, the RUN indicator LED will flash quickly.
No. Parameter Name Setting Range Default
b1-08 Run Command Selection while in Programming Mode 0 to 2 0
No. Parameter Name Setting Range Default
b1-14 Phase Order Selection 0 or 1 0
No. Parameter Name Setting Range Default
b1-15 Frequency Reference Selection 2 0 to 4 0
No. Parameter Name Setting Range Default
b1-16 Run Command Selection 2 0 to 3 0
No. Parameter Name Setting Range Default
b1-17 Run Command at Power Up 0 or 1 0