5.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual 201
Parameter Details
5
information is not listed on the motor nameplate, contact the motor manufacturer to find out the correct value for the
motor leakage inductance.
Setting the Motor Iron-Core Saturation Coefficient 1, 2
E2-07 and E2-08 are set when Auto-Tuning is performed.
Setting the Motor Mechanical Loss
The drive only requires this information when using Closed Loop Vector Control. The drive compensates for the degree
of mechanical loss with torque compensation. Although E2-09 rarely needs to be changed, adjustment may benefit the
following circumstances:
When there is a large amount of torque loss due to motor bearing friction.
When there is a large amount of torque loss in a fan or pump application.
Setting the Motor Iron Loss for Torque Compensation
This value only needs to be set when using V/f Control. Enter this value in watts to E2-10. The drive uses this setting to
improve the precision of torque compensation.
E3: V/f Pattern for Motor 2
These parameters set the V/f pattern used for motor 2. Refer to Setting 16: Motor 2 selection on page 219 for details on
switching motors.
Note: As the function for switching between two motors cannot be used with a PM motor, the E3- parameters will be hidden when
a PM motor control mode is selected (A1-02 = 5, 6, or 7).
E3-01: Motor 2 Control Mode Selection
Selects the control mode for motor 2. A control mode for PM motors cannot be selected for motor 2.
Setting 0: V/f Control
Setting 1: V/f Control with PG
Setting 2: Open Loop Vector Control
Setting 3: Closed Loop Vector Control
Note: Protection from motor overload (oL1) is determined by L1-01, just as it is for motor 1.
E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 as shown in Figure 5.54.
Note: Certain E3- parameters might not be visible depending on the control mode. Refer to Parameter Table on page 400.
No. Parameter Name Setting Range Default
E3-01 Motor 2 Control Mode Selection 0 to 3 0
No.
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<2> Default setting is determined by the control mode selected for motor 2 (E3-01).
<3> The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2).
<4> Parameter ignored when E3-11 and E3-12 are set to 0.0.
Parameter Name Setting Range Default
E3-04
Motor 2 Max Output Frequency
40.0 to 400.0 Hz <2>
E3-05
Motor 2 Max Voltage
0.0 to 255.0 <1> <1> <2>
E3-06
Motor 2 Base Frequency 0.0 to [E3-04]
<2>
E3-07
Motor 2 Mid Output Frequency 0.0 to [E3-04]
<2>
E3-08
Motor 2 Mid Output Frequency Voltage
0.0 to 255.0 <1> <1> <2>
E3-09
Motor 2 Minimum Output Frequency 0.0 to [E3-04]
<2>
E3-10
Motor 2 Minimum Output Frequency Voltage
0.0 to 255.0 <1> <1> <2>
E3-11
Motor 2 Mid Output Frequency 2 0.0 to [E3-04]
0.0 Hz <4>
E3-12
Motor 2 Mid Output Frequency Voltage 2
0.0 to 255.0 <1> 0.0 V <1> <3> <4>
E3-13
Motor 2 Base Voltage
0.0 to 255.0 <1> 0.0 V <1> <3>

Table of Contents

Other manuals for YASKAWA A1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 Series and is the answer not in the manual?

YASKAWA A1000 Series Specifications

General IconGeneral
SeriesA1000
TypeAC Drive
AltitudeUp to 1000m without derating
Output Frequency0-400 Hz
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Communication OptionsModbus, DeviceNet, Profibus, Ethernet/IP
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Horsepower0.5 to 1000 HP
Power Range0.4 - 630 kW (varies by voltage and model)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Cooling MethodFan Cooled
SafetySafe Torque Off (STO)