4.2 Using the Digital Operator
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual 89
Start-Up Programming
& Operation
4
ALARM (ALM) LED Displays
Table 4.2 ALARM (ALM) LED Status and Contents
LO/RE LED and RUN LED Indications
Table 4.3 LO/RE LED and RUN LED Indications
Figure 4.3
Figure 4.3 RUN LED Status and Meaning
Figure 4.4
Figure 4.4 RUN LED and Drive Operation
State Content Display
Illuminated When the drive detects a fault.
Flashing
When an alarm occurs.
When oPE is detected.
When a fault or error occurs during Auto-Tuning.
Off Normal operation (no fault or alarm).
LED Lit Flashing Flashing Quickly <1>
<1> Refer to Figure 4.3 for the difference between “flashing” and “flashing quickly”.
Off
When source of the Run command
is assigned to the digital operator
(LOCAL)
––
Run command to be given from a device other
than the digital operator (REMOTE)
During run
During deceleration to stop
When a Run command is input and
frequency reference is 0 Hz
While the drive is set for LOCAL, a
Run command was entered to the
input terminals after which the drive
was then switched to REMOTE.
A Run command was entered via
the input terminals while not in the
Drive Mode.
During deceleration when a Fast
Stop command was entered.
The drive output is shut off by the
Safe Disable function.
While the drive was running in the
REMOTE mode, the STOP key was
pushed.
The drive was powered up with b1-
17 = 0 (default) while the Run
command is active.
During stop
Examples
Flashing
ON ON
ON
ON ON
ON
1 s
Flashing
quickly
common_TM
only
/
Drive output frequency
during stop
Frequency setting
OFF
ON
Flashing
OFF
OFF
RUN LED
RUN
0 Hz
6 Hz
RUN
STOP
STOP
common_TM
only

Table of Contents

Other manuals for YASKAWA A1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 Series and is the answer not in the manual?

YASKAWA A1000 Series Specifications

General IconGeneral
SeriesA1000
TypeAC Drive
AltitudeUp to 1000m without derating
Output Frequency0-400 Hz
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Communication OptionsModbus, DeviceNet, Profibus, Ethernet/IP
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Horsepower0.5 to 1000 HP
Power Range0.4 - 630 kW (varies by voltage and model)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Cooling MethodFan Cooled
SafetySafe Torque Off (STO)

Related product manuals